DPS-100 Adjustable Differential Pressure Switch | iCoolheat

DPS-100 Adjustable Differential Pressure Switch | iCoolheat 1
  • DPS-100 Adjustable Differential Pressure Switch | iCoolheat 1
  • Place of Origin:China
  • Brand Name:iCoolheat
  • MOQ:5 pcs
  • Packaging Details:Standard Export Carton
  • Payment Terms:T/T
  • Supply Ability:20,000 pcs/month
  • Lead Time:7 days for standard models

DPS-100 is an adjustable differential pressure switch for HVAC filter, fan and airflow-status monitoring. It provides an SPDT switching contact when the pressure reaches the selected switching point. Choose the range to suit the application.

Key features

  • Six adjustable pressure-range options, from 20-200 Pa to 500-2500 Pa.

  • SPDT contact for switching and status monitoring.

  • Adjustable switching point with a pressure scale in Pa.

  • For air, non-flammable and non-aggressive gases.

  • IP54 protection rating.

Pressure-range options

OptionMeasuring / adjustable range
120-200 Pa
230-300 Pa
340-400 Pa
450-500 Pa
5200-1000 Pa
6500-2500 Pa

These are separate range options. Select the required version when ordering; one unit is not specified to cover all six ranges.

Technical specifications

ParameterDPS-100
Product typeDifferential pressure switch
Contact typeSPDT
Contact rating1.5 A (0.4 A) / 250 VAC
Maximum operating pressure2500 Pa
Medium / ambient temperature-20 to +85 °C
Pressure mediaAir, non-flammable and non-aggressive gases
Protection ratingIP54

HVAC applications

The DPS-100 air pressure switch can be used to monitor the pressure condition associated with ventilation filters, fans and airflow. A connected control system can use the switching contact for status indication or a pressure-threshold alarm, according to the system design.

Selection questions

How do I choose the pressure range?

Start with the switching pressure required by your filter, fan or ventilation design. Select a range that contains that setpoint and provides appropriate adjustment for the application. For example, a 20-200 Pa version and a 500-2500 Pa version serve different setpoint requirements.

Is 2500 Pa the adjustable range of every version?

No. 2500 Pa is the listed maximum operating pressure. The adjustable switching range depends on which of the six range options you select.

Does this switch provide a continuous pressure reading?

The specified output is an SPDT switching contact. Choose a differential pressure transmitter if your controller needs a continuous analogue or digital pressure measurement.

Can it monitor liquids or corrosive gases?

The specified media are air, non-flammable and non-aggressive gases. Do not select it for liquids or corrosive media on the basis of this specification.

What should I check before installation?

Check the selected pressure range, the contact load, the pressure medium and the environmental conditions. Confirm mounting orientation, pressure-port connections and the correct terminal arrangement using the instructions for the supplied version.

Request a quotation

Minimum order quantity: 5 pcs. Email info@heatcoolsmart.com with your required switching range, application and quantity.

Need a continuous pressure measurement? See the DPT-100 and DPT-600 differential pressure transmitters.