STE-100 duct and immersion temperature sensor and transmitter for HVAC, with analogue, passive or Modbus RTU options and IP65 protection. It measures air temperature in ventilation ducts or water temperature in an immersion installation. Select the output version, configured measuring range and probe length for your control system.
Duct and immersion temperature measurement for HVAC and building automation.
Catalogue temperature range: −40 to +140 °C (−40 to +284 °F).
Active-output accuracy: ±0.3 °C at 20 °C.
0–10 V, 0–5 V, 4–20 mA, passive sensor or Modbus RTU versions.
Housing IP65 / probe IP65; probe lengths from 50 to 230 mm.
| Parameter | STE-100 |
|---|---|
| Product type | Duct / immersion temperature sensor and transmitter |
| Temperature measuring range | −40 to +140 °C (−40 to +284 °F) |
| Accuracy | ±0.3 °C for active output, at 20 °C |
| Output options | 0–10 V / 0–5 V / 4–20 mA / passive temperature sensor |
| Digital interface option | Modbus RTU |
| Protection rating | Housing IP65 / Probe IP65 |
| Probe length | 50–230 mm |
Output signals are alternatives for the selected model, not simultaneous outputs from every unit. Confirm the ordered measuring range and probe length before purchase.
Use the STE-100 duct temperature sensor in ventilation and air-handling systems where the controller requires an air-temperature input. For water-pipe temperature measurement, select the immersion installation and a suitable thermowell for the application. It can serve HVAC and building automation controllers when their input type matches the ordered sensor output.
| Version | Selection consideration |
|---|---|
| 0–10 V or 0–5 V | Match the voltage range to the controller’s analogue input and configure the corresponding temperature scaling. |
| 4–20 mA | Select a compatible current input and check the supply and loop-load requirements for the supplied version. |
| Passive temperature sensor | Match the sensing element and resistance characteristic to the controller. NTC 10 kΩ, NTC 20 kΩ, Pt100 and Pt1000 options are described in the English manual; specify the required element when ordering. |
| Modbus RTU | Use an RS-485 Modbus RTU-compatible controller and confirm the communication settings and register information for the supplied version. |
No. Voltage, current, passive sensing and Modbus RTU are version options. Specify the signal needed by your controller when requesting a quotation.
Provide the lowest and highest process temperatures and the range expected by the controller. The catalogue lists −40 to +140 °C; confirm the configured range of the ordered version rather than assuming every analogue version uses identical scaling.
The catalogue specifies ±0.3 °C for active output at 20 °C. This should not be treated as a guaranteed accuracy over the full temperature range or automatically applied to every passive sensing element.
Choose a length within the catalogue’s 50–230 mm range to suit the duct or immersion location. For water-pipe installation, confirm the required thermowell and its suitability for the medium, temperature, pressure and pipe connection. Do not assume a thermowell is included.
Check the actual input: 0–10 V, 0–5 V, 4–20 mA, the specified passive resistance element, or RS-485 / Modbus RTU. The controller’s input, scaling and communication configuration must match the supplied STE-100 version.
No. The catalogue’s housing and probe IP65 ratings are not a statement that the complete unit is suitable for continuous submersion. Keep the housing in its intended mounting environment and use a suitable immersion installation for water-pipe measurement.
MOQ: 5 pcs. Send your application, required temperature range, output type, probe length and quantity to info@heatcoolsmart.com. State whether duct mounting or water-pipe immersion installation is required.