SAE-261 room CO2 and temperature transmitter with LCD for HVAC, offering 0–2000 or 0–5000 ppm CO2 ranges and analogue or Modbus RTU options. It provides indoor carbon dioxide and temperature measurement for a compatible building automation controller. Specify the required CO₂ range and signal arrangement for the installation.
Combined room CO₂ and temperature transmitter with LCD.
CO₂ range options: 0–2000 ppm or 0–5000 ppm.
Catalogue temperature measuring range: −40 to +140 °C (−40 to +284 °F).
0–10 V, 0–5 V or 4–20 mA analogue output options.
Modbus RTU digital interface option.
15–35 V DC / 24 V AC supply; IP30 protection.
| Parameter | SAE-261 |
|---|---|
| Product type | Room CO₂ & Temperature Transmitter |
| CO₂ measuring range options | 0–2000 ppm or 0–5000 ppm |
| Temperature measuring range | −40 to +140 °C (−40 to +284 °F) |
| Analogue output options | 0–10 V / 0–5 V / 4–20 mA |
| Digital interface option | Modbus RTU |
| Power supply | 15–35 V DC / 24 V AC |
| Display | LCD |
| Protection rating | IP30 |
Ranges and output signals are selection options. Confirm the configured ranges, available analogue channels or digital values, display configuration and supply requirements of the supplied version.
The SAE-261 room carbon dioxide and temperature transmitter provides measurement inputs for HVAC monitoring and building automation in indoor spaces. A compatible controller can use the CO₂ reading as part of ventilation monitoring and the temperature reading for room-condition monitoring, according to the system design. Select an installation environment suitable for IP30 protection.
Choose a CO₂ span that covers the expected room concentration. Match 0–10 V or 0–5 V to a voltage input, or 4–20 mA to a current input. Confirm how CO₂ and temperature are assigned to the supplied outputs and match each channel’s scaling to the controller.
For Modbus RTU, obtain the applicable communication settings and register definitions for both measurements. Confirm the power and connection arrangement for the selected version before installation.
The catalogue identifies SAE-261 as a combined CO₂ and temperature transmitter, while SAE-260 is listed as a room CO₂ transmitter. Choose SAE-261 when both measurements are required, and confirm their availability on the ordered outputs or registers.
Choose by the concentrations the application must monitor and the controller’s scaling requirements. The wider 5000 ppm span does not by itself establish accuracy or resolution. Specify the range when ordering and confirm any field-adjustment capability.
The catalogue lists signal options without defining the number of channels or channel assignment. Specify whether the controller needs separate analogue signals or digital values, and confirm the supplied arrangement before purchase.
The catalogue labels it as the temperature measuring range. It does not separately establish enclosure operating conditions or accuracy across that span. Confirm the actual installation conditions and configured measurement range for the selected version.
Humidity measurement is not listed in the SAE-261 catalogue entry. Do not assume it is provided because another model uses a similar housing. Specify any additional measurement requirement for separate confirmation.
The catalogue entry does not give CO₂ or temperature accuracy. Provide the expected concentration, temperature and required tolerances for selection. The enclosure is IP30; choose a representative room location and confirm suitability where damp conditions or condensation are possible.
MOQ: 5 pcs. Email info@heatcoolsmart.com with your room application, CO₂ range, temperature requirements, output arrangement, controller input, available power and quantity.
Other CO₂ formats: SAE-260 room CO₂ transmitter and SAE-200 duct CO₂ transmitter.