WFS-100 water flow switch with SPDT contact and 1 inch NPT connection, for water, ethylene glycol and other non-hazardous liquids. It provides a switching input for liquid-flow status monitoring. Check the medium, operating pressure, temperature and electrical load before selection.
Water flow switch with SPDT contact.
Maximum liquid pressure: 1034 kPa (150 psig).
Liquid temperature range: 0–121 °C.
Contact rating: 16 A at 240 VAC for a non-inductive load.
1 inch NPT process connection.
For water, ethylene glycol and other non-hazardous liquids.
| Parameter | WFS-100 |
|---|---|
| Product type | Water Flow Switch |
| Contact type | SPDT |
| Maximum liquid pressure | 1034 kPa (150 psig) |
| Liquid temperature range | 0–121 °C |
| Contact rating | 16 A at 240 VAC, non-inductive load |
| Process connection | 1 inch NPT |
| Suitable media | Water, ethylene glycol and other non-hazardous liquids |
The WFS-100 water flow switch provides a contact signal for liquid-flow status monitoring in compatible water and HVAC piping systems. Liquid movement acts on the paddle mechanism and changes the contact state when the switching condition is reached. The connected controller or circuit determines the resulting indication or control action.
Provide the pipe size, normal flow, required switching condition and liquid properties. The 1 inch NPT connection is the listed process connection, not a guarantee of compatibility with every pipe size or flow range. Confirm the supplied paddle arrangement and installation requirements.
General installation checks include matching the flow direction, allowing the paddle to move freely, protecting the installation from damaging hydraulic shocks and verifying switching operation after installation. Exact straight-pipe lengths, paddle trimming, terminal assignments and adjustment procedures must follow instructions confirmed for the supplied WFS-100 version.
The catalogue specifies an SPDT contact, not a continuous flow transmitter output. Choose a suitable flow transmitter if the controller needs a measured flow-rate value.
The WFS-100 catalogue entry does not specify switching-flow values. Provide pipe size, liquid, expected flow and the required switching condition so the suitable paddle and setting can be confirmed. Do not apply another model’s flow table automatically.
The listed 16 A at 240 VAC rating is for a non-inductive load. It should not be treated as a motor or other inductive-load rating. Confirm the applicable contact load and control-circuit arrangement for the supplied switch.
The catalogue lists water, ethylene glycol and other non-hazardous liquids. Gas service, hazardous media or a different chemical application requires separate confirmation; do not infer suitability from the connection size.
No. Confirm the mating fitting, pipe size, paddle length, mounting orientation and clearance for the supplied switch. Exact adjustment and wiring details must come from the applicable product instructions.
Confirm process pressure and temperature, media compatibility, the correct paddle and flow direction, free paddle movement and the contact arrangement. Isolate electrical power before wiring, and check the switching operation under the intended flow conditions.
Email info@heatcoolsmart.com with the liquid, pipe size, normal flow, required switching condition, pressure, temperature, electrical load and quantity. Confirm minimum order quantity and delivery conditions with the quotation.
For liquid pressure measurement, see PTE-100 water pressure transmitter.