SAE-160 room carbon monoxide (CO) transmitter with LCD, offering 0–500 or 0–1000 ppm ranges and analogue or Modbus RTU options for ventilation monitoring. It provides a CO concentration input for a compatible building automation or ventilation controller. Select the range and output required by the application.
Room carbon monoxide transmitter with LCD.
CO measuring range options: 0–1000 ppm or 0–500 ppm.
0–10 V, 0–5 V or 4–20 mA analogue output options.
Modbus RTU digital interface option.
Power supply: 15–35 V DC / 24 V AC.
IP30 protection rating.
| Parameter | SAE-160 |
|---|---|
| Product type | Room CO Transmitter |
| Measured gas | Carbon monoxide (CO) |
| CO measuring range options | 0–1000 ppm / 0–500 ppm |
| Analogue output options | 0–10 V / 0–5 V / 4–20 mA |
| Digital interface option | Modbus RTU |
| Power supply | 15–35 V DC / 24 V AC |
| Display | LCD |
| Protection rating | IP30 |
Ranges and signals are selection options, not simultaneous outputs from every unit. Confirm the ordered range, signal, LCD configuration and supply requirements.
The SAE-160 carbon monoxide transmitter provides a CO measurement input for building automation and ventilation monitoring. The model-specific reference manual describes indoor ventilation applications including underground car parks. Confirm the installation environment and the requirements of the complete control system.
Choose the 0–500 ppm or 0–1000 ppm version according to the expected concentrations and the controller’s required scaling. The wider range does not establish better accuracy. Match 0–10 V or 0–5 V to a voltage input, or 4–20 mA to a compatible current input.
For Modbus RTU, confirm RS-485 connectivity and obtain the applicable register definitions and communication settings for the supplied version. Verify power, wiring and load requirements before connection.
No. SAE-160 is listed for carbon monoxide, CO. Carbon dioxide, CO₂, is a different measured gas. Choose the transmitter for the gas specified by the application.
Choose the span required by the monitoring application and controller. Confirm required accuracy and operating conditions separately. The catalogue lists the two spans as options without establishing field-adjustment capability.
The catalogue specifies a measurement transmitter and does not state stand-alone alarm functions or life-safety certification. Do not assume it replaces a required certified alarm or protective system. Confirm the complete system’s applicable requirements.
Request confirmed accuracy, calibration and maintenance requirements for the supplied version and operating conditions. The concentration range is not an accuracy specification, and a service interval should not be inferred from other products.
The listed protection rating is IP30. Check moisture, condensation and exposure at the intended location and confirm environmental suitability before selection. Its use in a ventilation system does not make the enclosure waterproof.
Match the selected analogue output and ppm scaling, or the Modbus communication configuration. Alarm thresholds, ventilation actions and sensor placement must be determined for the complete installation; they are not defined by the measuring range alone.
MOQ: 5 pcs. Email info@heatcoolsmart.com with the CO monitoring application, required range, output, LCD requirement, environment, controller input and quantity.
For carbon dioxide measurement instead, see SAE-260 room CO₂ transmitter.