STE-200 wall-mount temperature sensor and transmitter for HVAC, with −40 to +140 °C measurement, IP65 protection and output options to suit your controller. Select an analogue output, passive temperature sensor or Modbus RTU version to match the building automation system. The STE-200 is designed for wall mounting.
| Parameter | STE-200 |
|---|---|
| Product type | Wall Mount Temperature Sensor & Transmitter |
| Temperature measuring range | −40 to +140 °C (−40 to +284 °F) |
| Accuracy | ±0.3 °C for active output, at 20 °C |
| Output options | 0–10 V / 0–5 V / 4–20 mA / passive temperature sensor |
| Digital interface option | Modbus RTU |
| Protection rating | Housing IP65 / Probe IP65 |
| Mounting | Wall mount |
The signals listed are options for different versions. Specify the required output when ordering; do not assume every STE-200 provides all outputs simultaneously. Confirm the configured range for the supplied version.
The STE-200 wall-mount temperature sensor provides a temperature input for HVAC monitoring and building automation applications requiring this mounting format. Choose the mounting position according to the temperature you need to measure. The ordered signal must match the input requirements of the BMS, DDC or PLC.
| Option | What to check |
|---|---|
| 0–10 V / 0–5 V | Match the sensor’s voltage output to the controller’s analogue input range and temperature scaling. |
| 4–20 mA | Check that the controller accepts a current signal and confirm the supply and loop requirements of the selected version. |
| Passive temperature sensor | Confirm the exact sensing element and resistance characteristic supported by the controller before ordering. |
| Modbus RTU | Confirm the controller’s Modbus RTU support and obtain the communication settings and register information for the supplied version. |
The STE-200 is listed for wall mounting, while the STE-100 is listed for duct or immersion installation. Select by the measurement location and installation method. Do not select an installation method solely because the housings look similar.
No. Choose 0–10 V, 0–5 V, 4–20 mA, passive sensing or Modbus RTU to match the controller’s supported input. A passive sensor input is not interchangeable with an active voltage or current input.
The catalogue specifies ±0.3 °C for active output at 20 °C. It does not state this accuracy for every temperature or for every passive version. Provide your operating temperature and accuracy requirement when requesting a quotation.
Select a position representative of the temperature being monitored. Consider local heat sources, direct sunlight and nearby airflow that could make the reading unrepresentative. Follow the installation instructions supplied with the selected model.
No. The listed housing and probe protection is IP65; this is not a continuous-submersion specification. Choose the installation to suit the intended environment.
Provide the expected minimum and maximum temperatures, the controller’s input type, required accuracy, installation environment and quantity. For passive or digital versions, also confirm the sensing-element requirement or communication requirements.
MOQ: 5 pcs. Email info@heatcoolsmart.com with your application, required range, output type and quantity.
For duct or immersion installation, see the STE-100 duct / immersion temperature sensor and transmitter.