CTE-200 capillary frost thermostat for HVAC coil low-temperature protection, with a 1.0–7.5 °C switching range and SPDT contacts. 3 m version stocked. The adjustable frost protection switch uses a capillary sensing element to detect low-temperature conditions. Select the required capillary length and verify the contact load for the control circuit.
| Parameter | CTE-200 |
|---|---|
| Product type | Capillary Frost Thermostat |
| Switching temperature range | 1.0–7.5 °C |
| Switching differential | 4.5–5.5 °C |
| Contact type | SPDT |
| Contact rating | 5 (4) A, 250 VAC |
| Ambient temperature | −40 to +65 °C |
| Capillary length options and codes | 1 m (1) / 2 m (2) / 3 m (3) / 4 m (4) |
| Catalogue stock status | 3 m version only; confirm current availability when ordering |
The CTE-200 capillary frost protection thermostat is intended for low-temperature protection in HVAC applications. The CTE-2003 reference instructions describe use around hot-water coils, chilled-water coils and the surfaces of liquid or gas pipes.
The sensing element responds to low temperature along the capillary. The reference instructions describe the low-temperature contact opening when the temperature falls to the setpoint and reconnecting as temperature rises through the switching differential. Confirm the correct contact pair and operation for the supplied version.
| Length | Catalogue code | Availability note |
|---|---|---|
| 1 m | 1 | Confirm availability |
| 2 m | 2 | Confirm availability |
| 3 m | 3 | Only stocked length listed in the catalogue |
| 4 m | 4 | Confirm availability |
Choose a length suitable for the sensing route and the area to be monitored. The capillary is a sensing element, not an ordinary extension cable; do not cut, flatten or damage it.
No. The catalogue specifies an SPDT switching contact for low-temperature protection. It does not list 0–10 V, 4–20 mA or Modbus temperature output for this model.
The 1.0–7.5 °C range is the adjustable switching-temperature range. The 4.5–5.5 °C differential is the separation between the switching and return conditions. It is not a temperature-accuracy specification.
No. That is the listed ambient temperature range. The adjustable switching temperature remains 1.0–7.5 °C.
The catalogue lists 5 (4) A at 250 VAC. The CTE-2003 reference instructions identify 5 A for a non-inductive load and 4 A for an inductive load at 250 VAC. Verify the actual circuit load and the supplied switch rating before connection.
The catalogue lists 1, 2, 3 and 4 m options but states that only the 3 m version is stocked. Ask for availability and delivery time for the selected length rather than assuming every option is in stock.
Follow the instructions for the supplied version, avoid locations affected by unrelated hot or cold sources, and protect the capillary from flattening or damage. The CTE-2003 reference instructions warn that capillary damage can alter the switching behaviour. Isolate power before electrical work and verify the contact arrangement.
Email info@heatcoolsmart.com with your application, capillary length, required setpoint, circuit voltage, load type and quantity. Confirm current availability, minimum order quantity and delivery time with the quotation.
For continuous temperature measurement, see the STE-100 duct / immersion temperature sensor and transmitter.