THE-100 duct humidity and temperature sensor and transmitter for HVAC, with 0–100 %RH measurement and analogue, passive temperature or Modbus RTU options. It measures relative humidity and temperature in HVAC air ducts. Select the output combination and configured temperature range to match the controller and installation.
| Parameter | THE-100 |
|---|---|
| Product type | Duct Humidity & Temperature Sensor & Transmitter |
| Humidity measuring range | 0–100 %RH |
| Temperature measuring range | −40 to +140 °C (−40 to +284 °F) |
| Sensing-element protection | Conformal coating |
| Output options | 0–10 V / 0–5 V / 4–20 mA / passive temperature sensor |
| Digital interface option | Modbus RTU |
| Mounting | Duct mount |
| Protection rating | Housing IP65 / Probe IP30 |
The listed signals are version options, not simultaneous outputs from every unit. Passive sensing applies to the temperature element, not the humidity measurement. Confirm the supplied output combination and configured measuring range before ordering.
The THE-100 duct humidity transmitter provides humidity and temperature information for HVAC air-duct monitoring and building automation. Match its signals to the input requirements of the BMS, DDC or PLC. Select a representative sensing position and an installation environment suitable for the probe and housing.
The English manual lists voltage, current, passive-temperature and RS-485 / Modbus RTU configurations. It identifies the standard 4–20 mA version as three-wire, with a two-wire version available on request. Confirm the wiring and channel arrangement for the exact ordered configuration.
Passive temperature options listed in the manual include NTC 10 kΩ, NTC 20 kΩ, Pt100 and Pt1000. These must match the controller’s sensor input. The manual lists ±3 %RH humidity accuracy and ±0.3 °C temperature accuracy; confirm the applicable conditions and selected version for your required operating point.
The catalogue’s temperature range describes the product selection information. Confirm the actual configured range and analogue scaling of the supplied version rather than assuming every output version uses the full listed span.
Match 0–10 V, 0–5 V or 4–20 mA to the analogue input type and configure the correct humidity and temperature scaling. For Modbus RTU, confirm communication settings and register information. For passive temperature sensing, specify the exact element required by the controller.
No passive humidity option is listed. The passive option refers to temperature sensing; specify how the humidity signal and temperature signal are to be provided in the ordered version.
The English manual states that the standard version uses three wires and a two-wire version is available on request. Specify the required version and verify its supply and connection requirements before installation.
The catalogue distinguishes housing IP65 from probe IP30. Do not apply the housing rating to the probe. The 0–100 %RH measuring range and conformal coating do not establish that the probe is waterproof or suitable for condensation or immersion.
Provide the expected humidity and temperature conditions together with the required tolerance. The English manual lists ±3 %RH and ±0.3 °C, but accuracy conditions and the supplied configuration should be checked for the intended operating point. Do not treat resolution or measurement range as an accuracy guarantee.
Choose a location representative of the duct air being measured, considering local temperature gradients, moisture and installation access. Follow the instructions for the supplied version and confirm suitable operation where condensation may occur.
MOQ: 5 pcs. Send your application, humidity and temperature conditions, required outputs, controller input specification and quantity to info@heatcoolsmart.com. State any two-wire current-output or passive-temperature requirement explicitly.
For temperature-only duct measurement, see STE-100.